| General |
| Schleifenbauer PDUs (Power Distribution Units) are power strips for data centre purposes. It is a 100% Dutch product that is exclusively produced along customers specifications. PDUs can be configured for both 16A and 32A , in single phase and three phase systems. The PDUs can be monitored locally (LCD display) and remotely using the Schleifenbauer Gateway. (Download available on this page ) |
| |
Profile |
| Material |
100% anodised aluminium. |
Colour and print
|
Black with laser engraving
|
| Dimensions |
width 65mm (1,5 U), depth 52,6 mm |
| Form factor |
19” single |
19” double ( outlets on rear side ) |
| |
half 19” single (2 PDUs next to each other on 19” ) |
half 19” double
|
| |
Vertical up to 2300 mm |
| |
Outlets |
| Outlets, type |
C13
IEC 60320 C13
|
C19
IEC 60320 C19
|
Schuko
CEE 7/4
|
Schuko
FR CEE 7/5
|
BS
BS 1363
|
CEE 16A
IEC 60309
|
Wieland
GST18/3
|
| |
Exit leads with CEE connectors 16A/32A single phase and threephase |
| Outlets, amount |
depending on length of profile |
| |
Power lead
|
| |
3G2,5 for 1 phase 16A |
3G6 for 1 phase 32A |
| |
5G2,5 for 3 phase 16A |
5G6 for 3 phase 32A |
Connection location
|
Front Rear Side cover
|
| Connector |
Upon customer demand |
| |
Display |
| Details |
Graphical backlit LCD display. 4 orientations, user definable
Energy saver modus: Back-light time delay user definable
|
| Information |
Measure values per phase,for total PDU and (optional) individual outlets: energy total in kWh,energy subtotal in kWh, current in A, voltage in V, power in VA, power factor in %, temperature in °C, (optional) status switchted outlet, name PDU, location PDU, free programmable ID PDU, address op data bus, serial number, part number, unieque ID PDU, firmware version of PDU. |
| |
Input module |
| Details |
suitable for 16A/32A, single phase and three-phase |
| Energy consumption in operation |
1 Watt (display off), 1,5 Watt (display on) |
| measuring: |
|
| Energy total |
kWh, non-resettable by user, <1% deviation |
| Energy subtotal |
kWh, resettable by user only via databus |
| Current |
Ampere RMS (apparent current), < 0,5% deviation |
Current peak
|
Ampère RMS, user definable peak time window: 50-2500 ms |
| Voltage |
Volt, < 0,5% deviation |
Voltage dip
|
Volt, user definable dip time window: 50-2500 ms |
| Power |
Apparent power in VA |
| Power factor |
Percentage 0,0 - 100,0 % |
| Temperature |
xx,x °C , optional through external temperature sensor. (± 2° C) |
| Accuracy energy measuring |
IEC 50470: 3 Klasse C, +/- 1% accuracy |
| |
Output module |
| Details |
9 outlets each max 16A (9 x single phase of 3 x L1, L2, L3) |
| Energy consumption in operation |
1 Watt
|
measuring per outlet:
|
|
| Energy total |
kWh, non-resettable by user, <1% deviation |
| Energy subtotal |
kWh, resettable by user only via databus |
| Current |
Ampere RMS (apparent current), < 0,5% deviation |
Current peak
|
Ampère RMS, user definable peak time window: 50-2500 ms |
| Voltage |
Volt, < 0,5% deviation |
Voltage dip
|
Volt, user definable dip time window: 50-2500 ms |
| Power |
Apparent power in VA |
| Power factor |
Percentage 0,0 - 100,0 % |
| Nauwkeurigheid energie-metingen |
IEC 50470: 3 Klasse C, +/- 1% nauwkeurigheid |
| Max # modules per PDU |
5 (45 outlets) |
| |
Switch module |
| Details |
9 outlets each max 16A (9 x single phase of 3 x L1, L2, L3) |
| Energy consumption in operation |
1 Watt |
| Type of relais |
Bi-stable, energy consumption nihil |
| Start up sequence and delay |
3 sart-up modes: 0) manual: no automatic start-up 1) Sequential start-up with standard delay 2) individual delay per outlet. All delays are user definable. Protected against simultaneous start-up of all outlets
|
| Max # modules per PDU |
5 (45 outlets) |
| |
Certificates |
| |
CE |
|
|
|
|
|
|
| |
RoHS |
Restriction of Hazardous Substances |
| |
WEEE |
Waste Electrical and Electronic Equipment |
| |
EN-60950 |
Low voltage certificate
|
| |
EN-61000 |
EMC, emission and immunity
|